Main Detail
Range

TeSys

Product Name

TeSys D

Type of product or equipment
Name of the device
contactor application

Resistive load
Motor control

Job Category
Description of the poles
power pole contact composition
[Ue

Power circuit: <= 1000 V AC 25...400 Hz Power circuit: <= 300 V DC [Ie] rated operational current 200 A (at <60 °C) at <= 440 V

[Ie

200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit

motor power kW

40 KW at 220...230 V AC 50/60 Hz (AC-3)
75 KW at 380...400 V AC 50/60 Hz (AC-3)
80 KW at 415...440 V AC 50/60 Hz (AC-3)
90 KW at 500 V AC 50/60 Hz (AC-3)
100 KW at 660...690 V AC 50/60 Hz (AC-3)
75 KW at 1000 V AC 50/60 Hz (AC-3)
22 KW at 400 V AC 50/60 Hz (AC-4)

motor power HP (UL / CSA)
control circuit type

DC standard

control circuit voltage
Auxiliary contacts
[Uimp

8 KV conforming to IEC 60947

Overvoltage category

III

[Ith
nominal switching capacity Irms
rated breaking capacity

1400 A at 440 V for power circuit conforming to IEC 60947

[Icw

250 A 40 °C - 10 min for power circuit
580 A 40 °C - 1 min for power circuit
1200 A 40 °C - 10 s for power circuit
1400 A 40 °C - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit

fuse rating to be associated
average impedance

0.6 MOhm - Ith 200 A 50 Hz for power circuit

[Ui

Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified

electrical life
power dissipated per pole
Front cover
Mounting bracket
Standards

CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508

Product certifications

GL
UL
BV
RINA
CSA
GOST
CCC
LROS (Lloyds register of shipping)
DNV

connection mode
tightening torque

Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm

Operating time

20...35 ms closing
40...75 ms opening

security reliability level
Mechanical endurance
maximum control speed
Wave